Model |
CIO200-ECIO-8A |
Shell Material |
Aluminum alloy |
Shell color |
Metallic silver primary color |
Ptotect degree |
IP67, epoxy full potting |
External dimensions |
205mm×60mm×34.4mm |
Weight |
515g |
Operating temperature |
-25℃~70℃ |
Storage/transport temperature |
-40℃~85℃ |
Operating humidity |
5%~95% |
Storage/transport humidity |
5%~95% |
Operating atmospheric pressure |
80KPa~106KPa |
Storage/transport atmospheric pressure |
80KPa~106KPa |
I/O port fastening torque |
M12:0.5Nm |
Application environment |
Conforms to EN-61131 |
Vibration testing |
Comply with IEC60068-2 |
Shock testing |
Comply with IEC60068-27 |
Free fall testing |
Comply with IEC60068-32 |
Electromagnetic compatibility (EMC) |
Comply with IEC61000-4-2,-3,-4 |
Certification |
CE,RoHS |
Installation hole specifications |
Φ4.5mm×1 ;Φ5.5mm×1 |
Input polarity |
PNP |
Indicator light -I/O |
Green: The channel signal is normal. Red: The port power supply is short-circuited |
Indicator light -RUN |
Green: OP status; Green slow blinking: SAFEOP status; Green fast blinking: Pre-OP status; Off: Init status |
Indicator Light -PWR |
Green: The power supply of the module is normal. Red: The power supply of the module is reversed |
Connection Method |
2 × M12 D-code; 4- core hole holder; |
Physicallayer |
Ethernet |
Transmission speed |
10/100 Mbps, Full duplex |
Characteristics |
Compliant with protocol features |
Alarm function |
Diagnostic alarm, process alarm |
Minimum cycle time |
1ms |
Communication port fastening torque |
M12:0.5 Nm |
Power supply connection method |
M12, 5-core, L-code, male/female head |
SSystem power supply voltage us |
18 to 30 VDC (type.24VDC) |
Auxiliary power supply voltage ua |
18 to 30 VDC (type.24VDC) |
Total current Is |
12A |
Total current Ia |
12A |
Static operating current Ic |
≤150mA |
Power reverse protection |
There are |
Number of main station ports |
Up to 8 ports can be configured |
How the master station is connected |
M12, 5-core, A-code, female head |
Communication rate |
COM1:4.8KBps; COM2:38.4KBps; COM3:230.4KBps |
Port voltage L+ |
type.24VDC (via US) |
Port current L+ |
2A (via US) |
Master Station - Slave station communication distance |
≤20 m |
Enter quantity |
8 way, adaptive |
Signal "0" voltage |
0.3 ~ 5 VDC |
Signal "1" voltage |
12~30VDC |
Input current |
type.5mA (via US) |
Number of outputs |
8 way, adaptive |
Output port location |
X1~X8 |
Output Current |
Single channel 2A (via UA) |
Port protection |
Power supply short circuit protection, power supply port overload protection |
Indicator light -LINK |
Green: The link is normal; Yellow flash: Link is normal, data communication is normal; Off: The link is not established |
Indicator light -ERR |
Blinking red: A communication error occurs. Off: The module is working properly |
Indicator light -IO-LINK |
Green: port operation (running) status; Green fast blinking: The port is being connected or an incorrect device is running. Green slow blinking: the port is in the pre-operation state. Green Off: The port is closed |
Communication Protocol |
EtherCat protocol |